PRODUCT FILES

PT433

THREE-PHASE ASYMMETRY CONTROL RELAY

The device is used for protection of three-phase asynchronous motors from electrical power supply disturbances. It is typically employed in submersible pump protection systems.

It provides protection against absence of one or more of the three phases or the neutral, asymmetry (adjustable, 5-25%), over-voltage and under-voltage.

The device is used for protection of three-phase asynchronous motors from electrical power supply disturbances. It is typically employed in submersible pump protection systems.

It provides protection against absence of one or more of the three phases or the neutral, asymmetry (adjustable, 5-25%), over-voltage and under-voltage.

Neutral connection is required.

It is installed in an electrical panel on a standard relay socket.

The output relay is activated when the three phases of the power supply do not differ between them in percentage more than the user adjustable value and do not exceed 270VAC (phase voltage). In any other case, as well as in case of complete loss of a phase or of the neutral, the relay is deactivated. In any other case , as well as in case of complete loss of a phase (phase voltage under 130VAC), the relay is deactivated.

It is a digital device using a microcontroller.

  • power supply
    3 x 230V AC / 50Hz
  • relay outputs
    One changeover contact relay 10Α / 250V AC cat. AC1 
  • indications
    POWER ON and RELAY ON
  • connection socket
    Bulb type, 8p or 11p
  • protection
    Varistor (against overvoltage and lightning)
  • operation temperature
    -20 to +50 C
  • adjustments
    Assymetry: 5 - 25% Vnom
  • enclosure
    Plastic box / 42x89x94mm / IP41